Routine maintenance

(The following maintenance procedure is just for reference only)
 
VP/Deutz generator set daily maintenance work
Check the lubricating oil level and coolant level for every 8 hours.
Check any lubricating oil and coolant leakage for every 8 hours. Changing lubricating oil and filter for every 500 hours.
Changing fuel oil filter and fuel / water separator (if any) for every 500 hours.
Clean the air cleaner element for every 100 hours and change the air cleaner for every 500 hours.

VP/Cummins generator set daily maintenance work
Check the lubricating oil level and coolant level for every 8 hours.
Check any lubricating oil and coolant leakage for every 8 hours.
Changing lubricating oil and filter for every 250 hours.
Changing fuel oil filter and fuel / water separator (if any) for every 250 hours
Clean the air cleaner element for every 100 hours and change the air cleaner for every 250 hours.
 


   
   